Electromagnetic flowmeter consists of two parts: electromagnetic flow converter and electromagnetic flow sensor.
Type and composition of liquid electromagnetic flowmeter
Product composition of liquid electromagnetic flowmeter
Electromagnetic flowmeter consists of two parts: electromagnetic flow converter and electromagnetic flow sensor. The separated type also A special double-shielded cable is required to connect the converter to the sensor.
Liquid electromagnetic flowmeter product type
Liquid electromagnetic flowmeter is divided into two structural forms: integrated type and separate type. Can be used in specified explosion-proof places.
The sensor is available with 7 different electrode materials and 4 different lining materials.
Technical performance indicators of liquid electromagnetic flowmeter products
1. Hospitality standard: JB/T
2. Maximum flow rate: 15m/s
3. Nominal diameter: DN3, 6, 10, 15, 20, 25, 32, 40, 50, 65, 80, 100, 150, 200, 250, 300, 350, 400, 450, 500, 600, 700, 800, 900, 1000, 1200, 1400, 1600, 1800, 2000
4. Accuracy: 0.5%, 0.2%
5. Nominal pressure: 4.0MPA (DN
1.6MPA(DN
1.0MPA(DN
0.6MPA(DN
Other specifications and standards can be based on user requirements.
6. Materials:
Electrode forms and materials
Electrode forms and materials can be divided into standard type, scraper type, detachable type, and grounded electrode.
The electrode and ground electrode materials include molybdenum-containing stainless steel, Hastelloy B, Hastelloy C, titanium, tantalum, platinum-eloy, and stainless steel coated tungsten carbide.
Flange material: carbon steel.
Grounding ring material: stainless steel.
Door protection ring material: stainless steel, carbon steel.
7. Shell protection:
IP65:
IP68: only separate neoprene and polyurethane-lined sensors, and does not include explosion-proof structure.
8. Explosion-proof standards:
DN15-DN600 Integrated explosion-proof: md II BT4.
DN15-DN1600 Separate explosion-proof, the sensor and converter are installed in the corresponding hazardous area md II BT4.
DN15-DN1600 Separate type explosion-proof, the sensor is installed in the corresponding dangerous area, and the converter is installed in the safe area: md II BT4.
9. Connecting cable: Separate type electromagnetic flowmeter, the sensor and the converter are connected with a signal cable , the longest cable length should be less than 6100MM.
10. Converter performance:
Power supply: single-phase AC 85-265V, 45-63HZ, power.The power is less than 20W; DC power supply 11-40VD·C.
Converter display and programming operation: 4 membrane buttons can set and select all parameters, and an external terminal or PC (RS485, RS232 ) Converter setting programming, high-definition backlight LCD display, empty pipe detection, self-diagnostic function.
Digital communication: RS485, RS232, MODBUS, REMOTE, with lightning protection.
Output signal:
Current output: bidirectional two-way, fully isolated 0-10mA/4-20 mA; load resistance: 0-10 mA is 0-1.5K ohm, 4 -20mA is 0-750 ohms.
Frequency output: forward and reverse flow output, the upper limit of the output frequency can be set within the range of 1-5000 HZ. Bidirectional output of transistor collector with photoelectric isolation. The external power supply is not greater than 35V, and the maximum collector current is 250 mA when turned on.
Pulse output: forward and reverse flow output, the upper limit of the output pulse can reach 5000cp/s. The pulse equivalent is 0.001L-1.0m3/cP. The pulse width is automatically set to 20ms or square wave. Transistor open collector output with opto-isolation. The external power supply should not be greater than 35V, and the maximum current of the collector when turned on is mA.
Flow direction indication output: This flowmeter can measure fluid flow in both forward and reverse directions. And can determine the direction of fluid flow. It is specified to output +10V high level when forward flow is displayed, and to output 0V low level when reverse fluid flow is displayed.
Alarm output: two-channel photoelectrically isolated transistor open collector alarm output. The external power supply is not greater than 35V, and the maximum collector current is 250mA when turned on. Alarm status: empty fluid pipe, excitation disconnection, flow over limit.
Damping time: optional in steps from 0-100S.